Modes: |
Digital; choice of
Record or Diverse
Record/Totalizer
combination functions. |
|
Display: |
One 4-digit display
(std.); second display
optional; 0.56½ high,
red, seven segment LED;
3 button keypad;
automatic and decimal
point positioning; |
|
Decimal Positions: |
None, one, two or three
decimal places. |
|
Status Indicators: |
7 LED status indicators:
Out 1, 2; one green LED
pen 2 indicator; LED
indicators ALRM1 and
ALRM2. |
|
Chart: |
10½ circular chart; 100
charts furnished with
each instrument. Unless
otherwise specified,
charts shipped with
instrument are 0–100
range. 24 hour rotation
default setting. |
|
Chart Drive: |
DC Stepper Motor. |
|
Chart Rotation: |
User configurable from
0.1 and 999.9 hours per
revolution. |
|
Chart Range: |
Bottom and top of span
–9999 to 9999 units. |
|
Pen Type: |
One or two disposable
fiber tip pen. |
|
Pen Color: |
Pen 1 (red); Pen 2
(green). |
|
Memory Backup: |
Battery; 5 year minimum
life. |
|
Construction/Enclosure: |
Injection molded Noryl
case; acrylic window
cover. |
|
Operating Temp: |
32° to 122°F (0° to
50°C). |
|
Storage Temp: |
–40° to 149°F (–40° to
65°C). |
|
Humidity: |
0% to 90% non-condensing
R.H. |
|
Vibration: |
0.5 to 100Hz @ 0.2g. |
|
Electro Static
Discharge: |
No effect from 5000V
static charge over the
entire area. |
|
Power Consumption: 2 |
5VA max. |
|
Line Voltage: |
115V or 230VAC ±10%,
50–60Hz. |
|
Thermocouple: |
N/A. |
|
RTD: |
N/A. |
|
Volts: |
0–5 VDC*; 1–5 VDC*. |
|
DC Milliamps: |
4–20mA , 0–20mADC. |
|
DC Millivolts*: |
0–100mV (can be scaled
to any portion of this
range). |
|
* Accompanied by
removal of a shunt
resistor factory
installed on the input
terminals. |
|
Relay: |
SPST/SPDT; 115VAC 5.0A
Resistive, 1/8HP, 250VA;
230VAC 2.5A Resistive,
1/8HP, 250VA. |
|
SSR Driver: |
Open collector output;
short circuit protected
@ 100mA max; provides
4VDC @ 20mA or 3VDC @
40mA. |
|
Current: |
0–20mA or 4–20mA; 0–650
ohm maximum load. |
|
Process Alarm: |
Direct (High) or Reverse
(Low); 0 to 9999 units. |
|
Deviation Alarm: |
N/A. |
|
Deviation Band Alarm: |
N/A. |
|
Alarm Hysteresis: |
0–300 units (width of
hysteresis band). |
|
Input Measurement Error: |
mA, mV, and VDC ±0.25%
of scaled span or better
typically; ±1 least
significant digit @
25°C. |
|
Ambient Temperature
Error: |
0.01% of span per degree
C deviation from 25°C. |
|
Isolation: |
N/A. |
|
Chart Accuracy: |
±1% of chart span. |
|
Noise Rejection: |
Common Mode: 90dB
minimum; 24VAC maximum
for RTD input; 115VAC
max for other inputs.
Normal Mode: 85dB
minimum @ 60Hz or
greater. |
|
Transmitter Power
Supply: |
Provides up to 42mA of
current at 24 VDC. |
|
Communications Port: |
N/A |
|
Protocol: |
N/A |
|
Bit Rate: |
N/A |
|
Address: |
N/A |
|
Safety: |
UL 1092 File E67237; CSA
Spec C22.2 File LR39885,
CE EN61010-1 1993/1995. |
|
Immunity: |
CE EN50082-1:1992 |
|
Emissions: |
CE EN55011:1991 |
|
Limit Device: |
N/A |
|
Other: |
ISO 9002 registered. |
|
Width: |
15.13" (384mm). |
|
Depth: |
3.63" (92mm). |
|
Height: |
13.19" (335mm). |
|
Weight: |
20 lbs (9.1kg). |
|
Mounting/Mounting
Position: |
Panel or wall. |
- 24V DC power
supply option.
- 115 or 230VAC
input option.
- Door lock and
sealed
conduit/connector
option.
- NEMA 3
protection optional.
- Totalizing flow
option.
|
|
|
|
|