Transmitters

Transmitters are used to send signals from one source to another.  Transmitters are available in both analog form (one analog signal in to another analog signal out) and digital (analog signal in to digital signal out).  In addition some transmitters provide rescaling and transmission to multiple sources.

 

The following are some examples of transmitters offered by Advanced Industrial Systems, Inc. 

 

 

TC Transmitter - SG 3011

Thermocouple Type
Temperature Range °C
Type J
-40° ~ +760°
Type K
0° ~ +1000°
Type T
-100° ~ +400°
Type E
0° ~ +1000°
Type R
+500° ~ +175
Type S
+500° ~ +1750°
Type B
+500° ~ +1800°
Type N
-100° ~ +1300°
Type C
0° ~ +2000°
Type L
-200° ~ +800°
Type M
-200° ~ +100°
Type L2 (DIN 43710)
-200° ~ +900°
  • Voltage Output: 0 -10V      Drive : 10mA max.
  • Current Output: 0 -20mA
  • Output impedance: <50Ω
  • CJC offset adjustable
  • OPEN Thermocouple detection
  • -3dB Band Width: 5.24Hz
  • Isolation (three way): 3000 Vdc
  • Overload protection: 240 Vrms
  • Accuracy: ±0.2% of full range
  • Stability (temperature drift): ±2°
  • Supply Voltage: 10~30 Vdc
  • Power Consumption: 1.44W
 

 

RTD Transmitter - SG-3013
  • Input Type: Pt, Ni
  • RTD Type and Temperature Ranges:
    Pt100 α=0.00385
    Pt100 α=0.003916
    Ni 120
    Pt1000 α=0.00385
    Pt100
    -100°
    to
    +100°
    a =0.00385
    Pt100
    to

    +100°

    a =0.00385
    Pt100
    to

    +200°

    a =0.00385
    Pt100
    to

    +600°

    a =0.00385
    Pt100
    -100°
    to
    +100°
    a =0.003916
    Pt100
    to

    +100°

    a =0.003916
    Pt100
    to

    +200°

    a =0.003916
    Pt100
    to

    +600°

    a =0.003916

    Ni120

    -80°
    to
    +100°
     

    Ni120

    to

    +100°

     
    Pt1000
    -200°
    to
    +600°
    a =0.00385
  • Stability
    Zero drift : ± 0.5uV/°C
    Span drift: ±25uV/°C
  • Noise Rejection
    -3dB Bandwidth : 5.24Hz
    CMR @ 50/60 Hz: 150 dB min
    NMR @ 50/60 Hz: 100 dB
    Isolation: 3000 V rms
  • Input Connections : 2/3/4 wires
  • Voltage Output : 0 - 5V,0 - 10V
    Drive : 10mA max.
    Output impedance : <50Ω
  • Current Output (Source): 0 - 20mA
  • Accuracy : ±0.2% of full range
  • Supply Voltage : 10~30Vdc ±10%
Head Mounted Industrial TC and RTD Transmitter
  • Designed to provide a 4 - 20 mA output from a TC or RTD
  • Convenient Head Mount  
  • Loop powered
  • Linear output with Cold Junction Compensation (TC)
Thermistor Transmitter
  • Designed for OEM instruments.
  • Provides Linearization for 2252 ohm YSI B Curve Thermistors or 2252 ohm US Sensor J curve thermistors and probes
  • 4 - 20 mA output
  • Converts non-linear thermistor curve to a linear output
I would like you to
Name
Company
Address
City, State, Zip
Country
Phone Number
Fax Number
E-Mail
Comments
 
Home Page          Site Index          Contact Us          Applications Notes and Tables          Products       On Line Order
Advanced Industrial Systems, Inc.
1-800-532-2477         Fax:  1-502-228-0127       Sales@AdvIndSys.com

American Express

Visa

Mastercard

Discover

Copyright 1997 - 2008 Advanced Industrial Systems, Inc. All rights reserved.
Last modified: Tuesday July 22, 2008.