West 8080-8081
1/8 DIN Dual Color Temperature Indicator

 

Temperature Control Applications Notes
All West Controllers
All CAL Controllers

West 8080 

 

Quick Specs...

  • Large Five Digit Display
  • Color Change On Alarm
  • Min/Max Value Hold
  • 2 Process Alarms
  • Security Lock
  • Process Transmitter PSU
  • PV retransmit option
  • RS485 comms option
Features
Output Configuration: Up to 3 total., max 2 for Alarms, max 1 for retransmission of PV
Alarm Types: Process high, process low, direct acting, process high, process low reverse and logical OR
Viewable Values: Process variable, alarm values, maximum value, minimum value and elapsed time since reset
Human Interface: 4 button operation, 5 digit 18mm high colour change display, plus set-up and alarm indicators

Temperature Version
Input: J, K, R, S, T, B, & N Thermocouple, 3 or 4 Wire PT100, 50. per lead maximum (balanced)
Impedance: >100MΩ for Thermocouple
Accuracy: +/- 0.1% of input span +/- 1 LSD (T/C CJC better than 0.5°C)
Sampling: 4 per second, 14 bit resolution
Sensor Break Detection: <2 secs, all alarms activate

DC Process Version
Input: 0-20/4-20/10-50mA, 0-5/1-5/0-10/2-10V, +/-100mV, +/-1V, +/-10V
Scaling: -19999 to 99999, dec point as required. Up to 10 scaling points for non-linear applications
Impedance: >100KΩ for mV range, >950KΩ for V ranges, 10Ω for 20mA ranges and 1Ω for 50mA range
Accuracy: +/- 0.01% of input span typical (+/- 0.05% max) +/- 1 LSD
Sampling: 10 per second, 14 bit resolution
Sensor Break Detection: <2 secs (except zero based ranges), all alarms activate
Totalising of PV by Interval: Seconds, minutes or hours
Transmitter Power Supply: 20-28V DC (24V nominal), max load 910Ω (22mA at 20V). Fitted as standard

Outputs & Options
Alarm 1: Open collector NPN transistor (30VDC 100 mA max) and relay (Contacts SPDT 3Amp)
Alarm 2: Open collector NPN transistor (30VDC 100mA max) fitted as standard. Optional relay
(Contacts SPDT 3Amp resistive at 240VAC/5Amp at 110V), non-latching
Retransmit Output: 0-20/4-20mA into 500Ω max, 0-10/0-5V into 500Ω min. Accuracy typically +/- 0.25% 250mS update
Digital Input: External security lock (also Tare function on Process Version). Volt free or TTL compatible
Communications: 2 wire RS485, 1200 to 9600 baud. ASCII protocol

Operating & Environmental
Temperature & RH: 0 to 55°C (-20 to 80°C storage), 20% to 95%RH non-condensing
Power Supply: 100 to 240V 50/60Hz 7.5VA (optional 20 to 50V AC 7.5VA/22 to 55V DC 5W)
Front Panel Protection: IEC IP66 (Behind panel protection is IP20)
Approvals and Certification: CE, UL & UlC

 

 
Name
Company
Address
City, State, Zip
Country
Phone Number
Fax Number
E-Mail
Additional Information

 

 
Home Page      Site Index      Contact Us      Applications Notes and Tables      Products      Manuals      On Line Order